Parameter (codelevel: operator) – Burkert Type 8620 User Manual

Page 135

Advertising
background image

mxCONTROL Type 8620


Page 135

Parameter (CodeLevel: Operator)

Parameter

Abbrevia-
tion
(menu)

Value range

Default values

(after successful download of Cfg-
File)

Channel 1
Pre-bleed limit
(in combination with
COND_CONTROL and
COND_PI)

PB

0 … 99999
(The unit is defined by the
unit of the process value of
the linked conductivity
module)

Scal- + ((Scal+ - Scal-)/2)
Centre of the input range (Scal- …
Scal+) of the assigned conductivity
module, e.g.:
Scal- = 0 µS, Xo = 1000 µS
PB default value = 500 µS

Note!

If the feed water quality is unknown, the maximum process value less 50 µS should be chosen

as Pre-bleed limit value. (e.g.: PB = max. PV - 50 µS)

Pre-bleed limit
(only in combination with
COND_CONTROL_RATIO
and COND_PI_RATIO)

PB ratio

-99999 ... 1.0
(The unit is defined by the
unit of the process value of
the linked conductivity
module)

-50.0

Max. duration of the pre-
bleed phase (*)

+TmPB

1 ... 180 min

180 min

Delay after Main dose

Tm1

0 … 180 min

1 min

Delay after Post dose

Tm2

0 … 180 min

1 min

Module output during
dosage

CMD on

0 … 100 %
0 … 100 % (if binary output)

100 %

Dosing Events
Selection of the day for parameterizing dosing events of this day
by selection of week (week 1 or 2) first,
then by selection of week day (Monday, Tuesday, …, Sunday)
Enable/Disable all dosing
events of a day

Dosing
Events 1-8

enable/disable disable

Dosing Event 1

Dos 1

Dosing Event 2

Dos 2

… …

Dosing Event 8

Dos 8

Dosing Event X
Enable/Disable dosing
Event X

enable/disable

disable

Start Time

Start

00:00 … 23:59

00:00

Dosing Time (Duration)

Tdose

1 … 180 min

1 min

Channel 2
All parameters of channel 1 are also available for channel 2 if the channel mode ChMode is set to dual.
(*) will be only displayed if the parameter “TmPB” is configured as “Yes” in the menu „Configuration“

The following figure shows the steps for the parameterizing of the dosing timer.