14.4

Corrosion Display (CORROSION-DISPLAY)

The corrosion display indicates the corrosion rate measured by the corrosion transmitter. Although
this function is not used directly for control purposes, it provides useful system status information.

These modules
are explained
below.

Figure 47: CORROSION_DISPLAY

Acid Stop Limit (ASL)

If the corrosion rate exceeds the predefined value, the Acid Stop Limit ASL, the ASL alarm for this
Function

is activated and the general alarm output is triggered. The ASL alarm is disabled again if the

process value is less than the ASL minus the ASL-hysteresis.

The ASL-Alarm can be used in combination with the controller modules PH_ACID_CAUS and
PH_ACID_OR_CAUS as additional failsafe for preventing overdosing of acids or bases. Hereby
both acid and caustic outputs (if existing) of the connected pH controller modules are set to "0" (shut
off), as long as the ASL-Alarm is active. If the system switch override for this module is configured and
becomes active (stand-by), the ASL alarm is disabled again.

Refer also to the description of the pH Controller Modules in chapter 14.5.1 and 14.5.2.

Processdata and Data Logging

Display-Presentation

Displayed data

Abbre-
viation
(menu)

Full

Screen

Trend

chart

Line

Data-

Log.

Notes

Process value

PV

x x x

Acid Stop Limit

ASL

x

x

Data Logging: Only
ASL alarm

Parameter (CodeLevel: Operator)

Parameter

Abbrevia-
tion
(menu)

Value range

Default values

(after successful download of
Cfg-File)

Acid Stop Limit

ASL

Scal- …Scal+ of the assigned input Scal- + ((Scal+ - Scal-) /2)

ASL hysteresis

Hyst

0.1 ... 10.0 % of input range

1.0 %

Configuration (Code Level: Specialist)

Configuration

Access
via
Cfg.-
menu

Access
via XML-
Cfg.-File

Abbreviation
(menu)

Value range

Default values

(after factory reset or
at start of Cfg-File-
Download)

Module active/not active rw

rw

Module

On/Off

Off

System switch override

rw

rw

SSOR

Yes / No

No