Configuration – Burkert Type 8620 User Manual

Page 83

Advertising
background image

mxCONTROL Type 8620


Page 83

Potentialfree binary input as "Flow Switch"

logical value

input voltage

Input signal:
Not inverted (Inv = No)

Input signal:
Inverted (Inv = Yes)

Open contact (*)

0 / Ok

1 / No Flow

0 … 4.5 V (*)
13 … 35 V (*)

1 / No Flow

0 / Ok

(*) The input voltage has to be applied continuously in the according range longer than the parameterized
delay time, before the logical value is accepted or changes.

Frequency- or 4-20mA-input as “Flow Switch”

input value

logical value

<

SP No Flow (**)

1 / No Flow

>=

SP No Flow (**)

0 / OK

(**) The input value has to be available according to the requirement (< or >=) longer than the parameterized
delay time, before the logical value is accepted or changes.

Configuration

Configuration
Flow Switch

Access
via Cfg.-
menu

Access
via XML-
Cfg.-File

Abbre-
viation
(menu))

Value range

Default values

(after factory reset or at
start of Cfg-File-
Download)

"Flow Switch" function
Enable/Disable

rw rw Flow

Switch

On/Off Off

Set point (*) No Flow

rw

rw

SP

-99999 … 99999
(in the unit of
assigned input)

0.0

Delay time

rw

rw

Delay

0 … 1800 s

1.0 s

Input r

rw

Input

DigIn 1, DigIn 2,
DigIn 3, DigIn 4,
No Input

No Input

(*) will be only displayed if a 4-20mA or frequency input is selected as „Flow switch“ input