Output override, Processdata and data logging, Parameter (codelevel: operator) – Burkert Type 8620 User Manual

Page 124: Configuration (code level: specialist)

Advertising
background image

mxCONTROL Type 8620


Page 124

Output Override

The output of this module is influenced at certain states (see figure).

Automatic

Manual

Operation
mode

Manual
Output
Value

0

1

Sensor-/Input
fault

Safety
Output
Value

Module

Output CMD

0

1

System
Switch

0 %

0

1

Flow
Switch

0 %

Output from

Output Limiter

System Switch
override function
can be enabled
or disabled

Flow Switch
override function
can be enabled
or disabled

Sensor-/Input
fault of assigned
Flow-Input

Figure 62: Output override (OPEN_PROP).

Processdata and Data Logging

Display-Presentation

Displayed data

Abbre-
viation
(menu)

Full

Screen

Trend

chart

Line

Data-

Log.

Notes

Flow Process value

PV

x x x

x

Module output

CMD

x x

x

Parameter (CodeLevel: Operator)

Parameter

Abbrevia-
tion
(menu)

Value range

Default values

(after successful download of Cfg-
File)

Lower output limit

Lim-

0.0 … Lim-

0.0 %

Upper output limit

Lim+

Lim+ … 100.0 %

100.0 %

Safety output value

CMDsafe

0.0 … 100.0 %

0.0 %

Configuration (Code Level: Specialist)

Configuration

Access
via Cfg.-
menu

Access
via XML-
Cfg.-File

Abbre-
viation
(menu)

Value range

Default values

(after factory reset or at
start of Cfg-File-
Download)

Module active/not active

rw rw Module

On/Off Off

System switch override

rw

rw

FSOR

Yes / No

No

Flow switch override

rw

rw

SSOR

Yes / No

No