14.10 Monitoring Process Values (MONITOR_PV)

This module is designed for external monitoring of up to two process values, e.g. via the optional
4…20 mA output

. But also the relay outputs or the transistor outputs can be connected.

It is possible to use an input signal as a source for another (controller) module and loop the same
input signal through for external monitoring.

This module can also be used for logging process values only without any output connected.

Figure 72:
MONITOR_PV

Each controller output signal is calculated depending on the configured input type.
If the input signal has a continuous input range (digital frequency input, analog inputs), the input range
will be represented linearly on the controller output. Please refer to the following table.

Input type

Input range

Controller
output

Controller output connected with
4...20 mA output

Digital binary input

0, 1

0 %, 100 %

4 mA, 20 mA

Digital pulse counter input

--

0 %

--

Digital frequency input

Scal- … Scal+

0 … 100 %

4 … 20 mA

Analog 4…20 mA input

Scal- … Scal+

0 … 100 %

4 … 20 mA

Analog Pt100 Input

Scal- … Scal+

0 … 100 %

4 … 20 mA

Processdata and Data Logging

Display-Presentation

Displayed data

Abbre-
viation
(menu)

Full

Screen

Trend

chart

Line

Data-

Log.

Notes

Process value 1

PV1

x x

x

x

Process value 2

PV2

x x

x

x

if ChMode = Dual

Module output 1

CMD1

x

x

x

Module output 2

CMD2

x

x

x

if ChMode = Dual

Advertising