Processdata and data logging, Parameter (code level: operator) – Burkert Type 8620 User Manual

Page 117

Advertising
background image

mxCONTROL Type 8620


Page 117

The internal timer counting the period of the maximum control output will be reset if the control output
is smaller than the maximum control output and the alarm has not yet been triggered. The maximum
output is determined by the parameter "Upper output limit Lim+".

The Maximum Output Timercan be enabled/disabled through the configuration. For a general
description of the MOT refer to chapter 14.1.5.

Processdata and Data Logging

Display-Presentation

Displayed data

Abbre-
viation
(menu)

Full

Screen

Trend

chart

Line

Data-

Log.

Notes

Process value

PV

x x x

x

Set point

SP

x x

x

Set point vs. Process value

SP/PV

x

Module output

CMD

x x

x

Alarm Maximum Output Timer

x

x

displayed only, if MOT
enabled and expired;
Data log in Module
output

Parameter (Code Level: Operator)

Parameter

Abbrevia-
tion
(menu)

Value range

Default values

(after successful down-
load of Cfg-File)

Sample Time

Tsample

0.05/0.1 … 60.0 s

0.2 s

Set point

SP

Scal- …Scal+ of the assigned input
SPLim- ... SPLim+ (if SP Limit is enabled)

Scal- +
((Scal+ - Scal-) /2)

Deadband

Dbnd

0 … 100.0 % of input range

1.0 %

Set point ramp

SP Ramp

Set point ramp

SP Ramp

Yes / No

No

Ramp rise: max. positive
SP change per minute (*)

D+

0.1 … 99999 pH/min

1 pH/min

Ramp rise: max. negative
SP change per minute (*)

D-

0.1 … 99999 pH/min

1 pH/min

Controller
Gain/amplification factor

Kp

0.001 … 9999.0 (in % / unit)

10.0

Reset time

Tn

0.1 … 9999.0 s

300.0 s

Lower output limit

Lim-

0.0 … Lim+

0.0%

Upper output limit

Lim+

Lim- … 100.0 %

100.0 %

Safety output value

CMDsafe

0.0 … 100.0 %

0.0 %

Maximum output timer (MOT)
Maximum output time (**) +Tm

1 ... 10800 s

10800 s

(*) will be only displayed if the parameter “SP Ramp” is set to “Yes”
(**) will be only displayed if the parameter “MOT” is configured as “Yes” in the menu „Configuration“

The pH controller output will be overridden with 0 % until the operator acknowledges the alarm
message with the soft key buttons in the process data menu, even if operation mode was
changed.