Page 74

13.1.3 Relay as PWM Output

Time t

T1

T2

T2

T2

Relay

dropout

Relay

activated

Relay Output (break contact)

with constant time (T2)

T1

T1

T1

Inv = No

Time t

T1

T2

T2

T2

Relay Output (break contact)

with constant time (T2)

T1

T1

Inv = Yes

Relay

activated

Relay

dropout

T2 = Tperiod

T1 – variable
T2 – constant

T2 = Tperiod

T1 – variable
T2 – constant

Pulse Width modulated
(PWM) outputs are used for
controlling the 2-point-valves
which are necessary for PI-
controlling of the conductivity.

The figure shows the
operational mode of the PWM
outputs.

Figure 22:
Relay as PWM output –
Operating mode: Normal or
inverted

13.1.4 Configuration (CodeLevel: Specialist)

Configuration

Access
via Cfg.-
menu

Access
via XML-
Cfg.-File

Abbre-
viation
(menu)

Value range

Default values

(after factory reset or
at start of Cfg-File-
Download)

Enabling / disabling
output

rw rw Output

On/Off

Off

Relay Output Type

rw

rw

Type

On/Off, PFM, PWM

enable/disable

Inversion of the output
signal

rw

rw

Inv

Yes / No

No

Additional configuration, if Relay Output Type = PFM selected
Unit pulse duration

rw

rw

Tpuls Unit

s, ms

ms

Pulse duration

rw

rw

Tpuls

1 … 9999

100 ms

Unit
Max. pulse frequency

rw

rw

Fmax Unit

/min, /h

/min

Max pulses per time

rw

rw

Fmax

1 … MAX
MAX <= 9999 and MAX
depend on the current
unit and pulse duration:
MAX = 1/Tpuls with
Tpuls in units of 1/(unit of
Fmax)

160/min

Additional configuration, if Relay Output Type = PWM selected
Unit of period duration

rw

rw

Tperiod
Unit

s, ms

s

period duration

rw

rw

Tperiod

1 … 9999 s or
100 … 9999 ms

10 s