Configuration (codelevel: specialist) – Burkert Type 8620 User Manual

Page 61

Advertising
background image

mxCONTROL Type 8620


Page 61

Configuration (CodeLevel: Specialist)

Configuration

Access
via
Cfg.-
menu

Access
via XML-
Cfg.-File

Abbre-
viation
(menu)

Value range

Default values

(after factory reset or
at start of Cfg-File-
Download)

Enabling / disabling
input

rw rw Input On/Off

Off

USE_KFACTOR

--

rw

--

0; 1

0

Unit K-Factor *)

rw

rw

K-Factor
Unit

(Pulses per) …
L, m³, Gal US, bbl US,
gal Imp, ft3, Pulse

Pulses per L

K-Factor *)

rw

rw

K-Factor

0.001 ... 9999.0

1.0

Frequency range:
Lower value**)

rw

rw

Freq-

0 Hz … Freq+

0.0

Frequency range:
Upper value**)

rw

rw

Freq+

Freq- … 2000 Hz

2000.0

Process value scaling:
unit

rw

rw

Scal Unit

Units of Chem.
Analysis, Volume, Flow,
Temperature, Misc; if *)
then only Flow***)

No Unit

Process value scaling:
low scaling value

rw

rw

Scal-

-99999 … Scal+

-99999

Process value scaling:
high scaling value

rw

rw

Scal+

Scal- … 99999

99999

Process value
scaling**): Sense of
action

rw

rw

ScalDir

Rise / Fall

Rise

Filter stage

rw

rw

Filter

0 ... 9

0

Process value alarm
Alarm mode

rw

rw

Mode

Off, Alarm,
Alarm & Warn

Alarm & Warn

Low alarm limit (****)

rw

rw

Alarm-

-99999 … Alarm+

-99999

High alarm limit (****)

rw

rw

Alarm+

Alarm- … 99999

99999

Alarm hysteresis (****)

rw

rw

AlarmHys

0.1 … 10.0 % of range
(Scal- … Scal+)

1.0 %

Low warning limit (****)

rw

rw

Warn-

Alarm- … Warn+

-99999

High warning limit (****) rw

rw

Warn+

Warn- … Alarm+

99999

Warning hysteresis
(****)

rw rw WarnHys

0.1 … 10.0 % of range
(Scal- … Scal+)

1.0 %

*) only visible if "Use K-Factor for Scaling" = 1
**) only visible if "Use K-Factor for Scaling" = 0
***) the units “P/m”, “P/s” are only accepted, if the unit pulses per “Pulse” is selected at “Unit K-Factor”;
other units are only accepted, if not the unit pulses per “Pulse” is selected at “Unit K-Factor”
(****) will be only displayed if the corresponding Alarm Mode is selected

Advertising