14.6

Dosing of oxygen absorption media

14.6.1 Flow and temperature-based dosing

(O2_SCAV_CTRL_RATIO)

This module permits the dosing of oxygen-absorbing substances which are added to the hot water
as anti-corrosive, based on the flow and temperature of the feed water).

These modules
are explained
below.

Figure 55: O2_SCAV_CTRL_RATIO

Flow-temperature dosing control (FT dosing control)

Flow-temperature dosing control determines the output signal proportionally to the flow of the feed
water and the oxygen dissolved in it - see the following figure.

The oxygen content is determined via the temperature of the feed water (see section "

Oxygen concentration"). For the calculation, the actual flow value is converted into a scaled flow
0…100% whereby 0% corresponds to the low scaling value Scal- and 100% to the high scaling value
Scal+ of the flow input.

Control output = a * b

with a … flow (scaled value)

b … oxygen concentration (scaled value)

Figure 56:
FT Dosing control