3 pulse counter inputs, 2 analog inputs, 1 4…20 ma inputs – Burkert Type 8620 User Manual

Page 62: Configuration (code level: specialists), A/d-conversion

Advertising
background image

mxCONTROL Type 8620


Page 62

12.1.3 Pulse Counter Inputs

The pulse counter inputs, for example, can be used in combination with the Batch Dosing modules.

The incoming pulses are counted and scaled for further processing per K-Factor. The K-Factor
specifies the amount of pulses per volume unit. The K-Factor can specified in different units - please
refer to the "Configuration" section (see below) for the available units.

Configuration (Code Level: Specialists)

Configuration

Access
via Cfg.-
menu

Access
via XML-
Cfg.-File

Abbre-
viation
(menu)

Value range

Default values

(after factory reset or at
start of Cfg-File-
Download)

Enabling /
disabling input

rw rw Input

On/Off

Off

Unit K-Factor

rw

rw

K-Factor
Unit

(Pulses per) …
L, m³, Gal US, bbl US, gal
Imp, ft3, Pulse

Pulses per L

K-Factor

rw

rw

K-Factor

0.001 … 9999.0

1.0

12.2 Analog

Inputs

The analog inputs are configurable either as 4…20 mA inputs or as Pt100 inputs via the configuration
file for defined hardware versions.

For details please refer to the following sections.

12.2.1 4…20 mA Inputs

Figure 16:
4…20 mA Input

A/D-Conversion

The enabled analog 4...20 mA inputs are sampled every 50 ms with a resolution of 10 bit in order to
convert the analog input signal to a digital value.

Additionally the enabled analog 4...20 mA inputs are checked after each sampling process on:

• input fault (current less than approx. 3.5 mA)
• sensor fault (current greater than approx. 20.5 mA)
• AD-fault (fault during sampling process).
• A calibration data fault is treated as an input fault.

Only the number of incoming pulses is indicated at pulse counter inputs in the menu item
"Process data" \ "Inputs". The display starts with 0 again if more than 99999 pulses are
counted.