Processdata and data logging, Parameter (codelevel: operator) – Burkert Type 8620 User Manual

Page 92

Advertising
background image

mxCONTROL Type 8620


Page 92

Processdata and Data Logging

Display-Presentation

Displayed data

Abbre-
viation
(menu)

Full

Screen

Trend

chart

Line

Data-

Log.

Notes

Process value

PV

x x

x

x

Process Value 2
(Set point External)

PV2

x

x

x

Only if
SP input = External

Set point

SP

x

x

x

Set point vs. Process value

SP/PV

x

Module output

CMD

x

x

x

Parameter (CodeLevel: Operator)

Parameter

Abbrevia-
tion
(menu)

Value range

Default values

(after successful down-
load of Cfg-File)

Sample Time

Tsample

0.05/0.1 … 60.0 s

0.2 s

Set point (*)

SP

Scal- …Scal+ of the assigned input
SPLim- ... SPLim+ (if SP Limit is enabled)

Scal- + ((Scal+ - Scal-)
/2)

Ratio set point (****)

Kx

0.001 … 9999.0

1.0

Set point ramp

SP Ramp

Set point ramp

SP Ramp

Yes / No

No

Ramp rise: max. positive
set point change per
minute (**)

D+

0.1 … 99999 (unit of process value input)

1

Ramp rise: max. negative
set point change per
minute (**)

D-

0.1 … 99999 (unit of process value input)

1

CutOff

CutOff

CutOff

Mode

Off / Cut- / Cut+ / Cut- & Cut+

disable

Lower CutOff threshold
(***)

Cut-

Scal- ... Scal+
(Scal- and Scal+ of process value input)

Scal-

Upper CutOff threshold
(***)

Cut+

Scal- ... Scal+
(Scal- and Scal+ of process value input)

Scal+

PID Controller
Deadband

Dbnd

0.1 … 10.0 % of input range

1.0 %

Gain/amplification factor

Kp

0.001 … 9999.0 (in % / unit)

1.0

Reset time

Tn

0.1 … 9999.0 s

9999.0 s

Derivation time

Tv

0.0 … 9999.0 s

0.0 s

Start point

X0

0.0 … 100.0 %

0.0 %

Lower output limit

Lim-

0.0 … Lim+

0.0 %

Upper output limit

Lim+

Lim- … 100.0 %

100.0 %

Safety output value

CMDsafe

0.0 … 100.0 %

0.0 %

(*)

will be only displayed if the parameter „SP Input“ is selected as „intern“ in the menu „Configuration“

(**)

will be only displayed if the parameter „SP Ramp“ is selected as „Yes“ in the menu „Parameter“

(***) will be only displayed if the selected „(CutOff) Mode“ supports the according parameter
(****) will be only displayed if the parameter „SP Input“ is selected as „External“ in the menu „Configuration“

Advertising