Processdata and Data Logging

Display-Presentation

Displayed data

Abbre-
viation
(menu)

Full

Screen

Trend

chart

Line

Data-

Log.

Notes

Process value System Channel

PV1

x x x

x

Process value System Channel
(in ppm)

PV1

x x

x

Only if TDS-Display
is configured

Process value Make-Up
Channel

PV2

x x x

x

Set point

SP

x x

x

Set point vs. Process value
System Channel

SP/PV1

x

Module output

CMD

x x

x

Alarm Maximum Output Timer

x

x

is displayed only if
MOT was enabled
and is expired;
Data log in controller
output

Parameter (Code Level: Operator)

Parameter

Abbrevia-
tion
(menu)

Value range

Default values

(after successful download of Cfg-File)

For Make-Up Channel:
Ratio

Kx

1.2 … 9.999

2.0

Offset

Offset

0 … 999.9 µS/cm

10 µS/cm

For System Channel:
Switching hysteresis

Hyst

0.1 ... 10.0 % of input
range

1.0 %

Safety output value

CMDsafe

0.0 ... 100.00 %

0.0 %

Maximum output timer (MOT)
Maximum output time (*)

+Tm

1 ... 10800 s

10800 s

For TDS-Calibration:
Conductivity value (**)

PV cal

1 ... 99999 (in units of
the assigned process
value input)

1000

TDS value (**)

TDS cal

1 ... 99999 ppm

800 ppm

(*) will be only displayed if the parameter “MOT” is configured as “Yes” in the menu „Configuration“
(**) will be only displayed if the parameter “TDS Disp” is configured as “Yes” in the menu „Configuration“

Configuration (CodeLevel: Specialist)

Configuration

Access
via
Cfg.-
menu

Access
via XML-
Cfg.-File

Abbreviation
(menu)

Value range

Default values

(after factory reset or
at start of Cfg-File-
Download)

Module active/not active rw

rw

Module

On/Off

Off

Inversion module sense
of action

rw

rw

InvMod

Yes / No

No

Pre-bleed and "Biocide
dosing output override"

rw

rw

Prebleed

Yes / No

No

TDS display

rw

rw

TDS Disp

Yes / No

No

System switch override

rw

rw

SSOR

Yes / No

No

Flow switch override

rw

rw

FSOR

Yes / No

No

Maximum Output Timer

rw

rw

MOT

Yes / No

No