Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual

Page 168

Advertising
background image

6–26

Parameters

Publication 1336 FORCE–5.18 ––March, 1999

387

Analog Output 1

[Analog Out 1]

Analog Out 1 converts a

±

32767 value to a

±

10V

signal. The digital value is linked to a 1336 FORCE
source parameter which provides a value that is
scaled and offset. The results are converted to a
voltage signal, where

±

2048 results in a

±

10V

output.

Parameter Number

387

Parameter Type

Read/Write, Sink

Display Units / Drive Units

±

32767

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

File – Group

Communication I/O – Analog Output

388

Analog Output 2

[Analog Out 2]

Analog Out 2 converts a

±

32767 value to a

±

10V

signal. The digital value is linked to a 1336 FORCE
source parameter which provides a value that is
scaled and offset. The results are converted to a
voltage signal, where

±

2048 results in a

±

10V

output.

Parameter Number

388

Parameter Type

Read/Write, Sink

Display Units / Drive Units

±

32767

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

File – Group

Communication I/O – Analog Output

389

Analog Output 3

[Analog Out 3]

Analog Out 3 converts a

±

32767 value to a

±

10V

signal. The digital value is linked to a 1336 FORCE
source parameter which provides a value that is
scaled and offset. The results are converted to a
voltage signal, where

±

2048 results in a

±

10V

output.

Parameter Number

389

Parameter Type

Read/Write, Sink

Display Units / Drive Units

±

32767

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

File – Group

Communication I/O – Analog Output

390

Analog Output 4

[Analog Out 4]

Analog Out 4 converts a

±

32767 value to a

±

10V

signal. The digital value is linked to a 1336 FORCE
source parameter which provides a value that is
scaled and offset. The results are converted to a
voltage signal, where

±

2048 results in a

±

10V

output.

Parameter Number

390

Parameter Type

Read/Write, Sink

Display Units / Drive Units

±

32767

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

File – Group

Communication I/O – Analog Output

391

SCANport Analog Select

[SP Analog Sel]

SP Analog Sel indicates which port (1 through 5) is
to receive the SCANport analog input value that
appears in parameter 338, SP Analog In.

Parameter Number

391

Parameter Type

Read/Write, Sink

Display Units / Drive Units

None

Factory Default

1

Minimum Value

1

Maximum Value

5

File – Group

Communications I/O – Analog Output

Enums

1 = Port 1

2 = Port 2

3 = Port 3

4 = Port 4

5 = Port 5

Advertising