Installing and Wiring Your ControlNet Adapter Board

Publication 1336 FORCE–5.18 ––March, 1999

The typical analog input connections for bidirectional operation can
be shown as follows:

COM (POWER SUPPLY COMMON)

IN + (ANALOG IN)

+ 10V

DC (POWER SUPPLY)

IN – (ANALOG IN)

18

REFERENCE POT
2.5 k

MINIMUM

TB21

17

– 10V

DC (POWER SUPPLY) 19

ADC

REVERSE

FORWARD

R

Reverse

Reverse

Relay

Forward

TO TE
(SIGNAL GROUND TERMINAL BLOCK)

Note: Connect to Only One Set of Inputs
IN4+ and IN4–
IN3+ and IN3–
IN2+ and IN2–
IN1+ and IN1–

The following table shows the analog input specifications:

Specifications:

Value:

Differential impedance

Greater than 1 Ohm

Single ended impedance

20K Ohm

Maximum voltage

±

10V

Analog Outputs

The ControlNet Adapter Board has 4 analog outputs that have a
range of

±

10V and a digital resolution of 12 bits. Chapter 2, Starting

Up, describes the parameters associated with scaling analog values.

The typical analog output connections can be shown as follows:

OUT (ANALOG OUT)

COM (ANALOG OUT)

TB21

DAC

0 to

±

10V

DC

1mA Maximum

100 Ohm
Maximum Impedance

TO TE
(SIGNAL GROUND TERMINAL BLOCK)

Note: Connect to Only One Set of Outputs
COM4 and OUT4
COM3 and OUT3
COM2 and OUT2
COM1 and OUT1