Troubleshooting

Publication 1336 FORCE–5.18 ––March, 1999

ControlNet Adapter Board fault and warning codes are five character
decimal numbers that have the following format:

S

A XXX

Source Designator

0 = Main Board Velocity Processor
1 = Main Board Current Processor
2 = Adapter Processor
3 = CNA Interface
4 = Reserved
5 = Reserved

Area Designator

0 = General
1 = Motor
2 = Inverter
3 = Motor Control
4 = Reserved Adapter
5 = External Device
6 = Communications
7 = Reserved
8 = Reserved
9 = Converter/Brake

Internal Fault Code

S

A

X

X

X

Both HIM and GPT displays indicate a fault or warning by showing
the adapter code and fault text. Fault text may be up to 16 characters
in length.

The following are the fault codes.

Fault text and

code:

Fault

type:

Description:

Suggested action:

Faults Cleared
24000

None

This entry in the fault or
warning queue is displayed
when you request a clear fault
command.

None

Adpt BRAM
Cksm
24009

Soft

There is a discrepancy between
the calculated checksum and the
saved checksum for the adapter
data.

Reset the drive. If the fault persists:

1. Execute a BRAM recall.

2. Execute a BRAM store.

3. Reset the drive.

4. Clear the faults.

When you are done with these steps,
verify all parameter values.