Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual
Page 176
6–34
Parameters
Publication 1336 FORCE–5.18 ––March, 1999
426
ICN WarningSelect
[ICN Warn Sel]
ICN Warn Sel dictates whether the ControlNet
Adapter Board will report a warning condition if a
PLC controller communications fault occurs.
If a bit is one and the corresponding bit in parameter
425 is zero, then the condition is reported as a
warning.
If a bit is zero and the corresponding bit in
parameter 425 is zero, then the condition is ignored.
Parameter Number
426
Parameter Type
Read/Write, Non–Linkable Sink
Display Units / Drive Units
Bits
Factory Default
47 (2Fh)
Minimum Value
0
Maximum Value
127 (7Fh)
File – Group
Diagnostics – Fault Select/Status
Communication I/O – Fault Select/Status
When adapter is used:
Enums
Bits 7–4 Bit 3 Bit 2 Bit 1 Bit 0
Res/Pgm/Test (Flt 36023)
0 = No drive warning
1 = Drive warning
Last State
0 = Data zeroed
1 = Last State
ICN Comm Loss (Flt 36021)
0 = No drive warning
1 = Drive warning
Class 1 Close
0 = No drive warning
1 = Drive warning
Bit 4: Class 3 Close
0 = No warning
1 = Drive warning
Bit 5: Class 1 Timeout
0 = No drive warning
1 = Drive warning
Bit 6: Class 3 Timeout
0 = No drive warning
1 = Drive warning
Bit 7: Reserved