ICN Fault Select

[ICN Flt Sel]

ICN Flt Sel dictates whether the ControlNet Adapter
Board will report a fault condition if a PLC controller
communications fault occurs.

If bit is one, the condition is reported as a soft fault.
If a bit is zero, parameter 426 is checked to see
whether a warning condition should be reported.

Parameter Number

425

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

Bits

Factory Default

47 (2Fh)

Minimum Value

0

Maximum Value

127 (7Fh)

File – Group

Diagnostics – Fault Select/Status

Communication I/O – Fault Select/Status

When adapter is used:

Enums

Bits 7–4 Bit 3 Bit 2 Bit 1 Bit 0

Res/Pgm/Test (Flt 36023)
0 = No drive soft fault
1 = Drive soft fault

Last State
0 = Data zeroed
1 = Continue Operation
Using Last State

ICN Comm Loss (Flt 36021)
0 = No drive soft fault
1 = Drive soft fault

Class 1 Close
0 = No drive soft fault
1 = Drive soft fault

Bit 4: Class 3 Close
0 = No drive soft fault
1 = Drive soft fault

Bit 5: Class 1 Timeout
0 = No drive soft fault
1 = Drive soft fault

Bit 6: Class 3 Timeout
0 = No drive soft fault
1 = Drive soft fault

Bit 7: Reserved