7–10

Troubleshooting

Publication 1336 FORCE–5.18 ––March, 1999

Fault text and

code:

Suggested action:

Description:

Fault

type:

Drv Types Differ
24010

Soft

There is a discrepancy between
the drive type on the base driver
board and the parameter 220
and 221 values in BRAM.

Reset the drive. If the fault persists:

1. Execute a BRAM recall.

2. Execute a BRAM store.

3. Reset the drive.

4. Clear the faults.

When you are done with these steps,
verify all parameter values.

I11 Drive Type
24011

Hard

The drive type code in Serial E2
on the base driver board is not a
valid code per the language
module table.

Replace the base driver board.

Main BRAM
Cksm
24012

Soft

There is a discrepancy between
the calculated checksum and the
saved checksum for the main
control board.

Reset the drive. If the fault persists:

1. Execute a BRAM recall.

2. Execute a BRAM store.

3. Reset the drive.

4. Clear the faults.

When you are done with these steps,
verify all parameter values.

SW Malfunction
24013

Hard

The integrity check on the board
software has failed.

Reset the drive. If the fault persists,
you may have to replace either the
ControlNet Adapter Board or the main
control board.

SW Malfunction
24014

Hard

The integrity check on the board
software has failed.

Reset the drive. If the fault persists,
you may have to replace either the
ControlNet Adapter Board or the main
control board.

SW Malfunction
24015

Hard

The integrity check on the board
software has failed.

Reset the drive. If the fault persists,
replace the ControlNet Adapter Board.

SW Malfunction
24016

Hard

The integrity check on the board
software has failed.

Reset the drive. If the fault persists,
replace the ControlNet Adapter Board.

SW Malfunction
24017

Hard

The integrity check on the board
software has failed.

Reset the drive. If the fault persists,
replace the ControlNet Adapter Board.

SW Malfunction
24018

Hard

The integrity check on the board
software has failed.

Reset the drive. If the fault persists,
replace the ControlNet Adapter Board.

AP SW/LM Rev
Err
24025

Soft

There is a ControlNet Adapter
Board software/language
module mismatch.

Verify the board software and language
module versions with Allen–Bradley.

Adapter Config
Err
24026

Soft

The ControlNet Adapter Board
has detected that the current
firmware revision does not
match the value stored in
NVRAM

Verify that the adapter board and
firmware revision is correct and
execute a BRAM store to save the
values.