Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual

Page 199

Advertising
background image

7–11

Troubleshooting

Publication 1336 FORCE–5.18 ––March, 1999

Fault text and

code:

Suggested action:

Description:

Fault

type:

No AP LM Exists
25023

Hard

The ControlNet Adapter Board
has detected that a language
module has not been installed
on the ControlNet Adapter
Board.

Reset the drive. If the fault persists,
replace the language module.

SP Pt1 Timeout
26038

Soft,
warning,
or none

The device connected to Port 1
of SCANport has been
disconnected.

Reconnect Device if desired.

SP Pt2 Timeout
26039

Soft,
warning,
or none

The device connected to Port 2
of SCANport has been
disconnected.

Reconnect Device if desired.

SP Pt3 Timeout
26040

Soft,
warning,
or none

The device connected to Port 3
of SCANport has been
disconnected.

Reconnect Device if desired

SP Pt4 Timeout
26041

Soft,
warning,
or none

The device connected to Port 4
of SCANport has been
disconnected.

Reconnect Device if desired.

SP Pt5 Timeout
26042

Soft,
warning,
or none

The device connected to Port 5
of SCANport has been
disconnected.

Reconnect Device if desired.

SP Comm Fault
26043

Hard

The integrity check on the board
hardware has failed.

Reset the drive. If the fault persists,
replace the ControlNet Adapter Board.

HW Malfunction
34001

Hard

The integrity check on the board
hardware has failed.

Reset the drive. If the fault persists,
replace the ControlNet Adapter Board.

HW Malfunction
34002

Hard

The integrity check on the board
hardware has failed.

Reset the drive. If the fault persists,
replace the ControlNet Adapter Board.

HW Malfunction
34003

Hard

The integrity check on the board
hardware has failed.

Reset the drive. If the fault persists,
replace the ControlNet Adapter Board.

HW Malfunction
34004

Hard

The integrity check on the board
hardware has failed.

Reset the drive. If the fault persists,
replace the ControlNet Adapter Board.

HW Malfunction
34005

Hard

The integrity check on the board
hardware has failed.

Reset the drive. If the fault persists,
replace the ControlNet Adapter Board.

SW Malfunction
34016

Hard

The integrity check on the board
software has failed.

Reset the drive. If the fault persists,
replace the ControlNet Adapter Board.