4–40

Using Unscheduled Messaging

Publication 1336 FORCE–5.18 ––March, 1999

The Continuous Parameter Link Write message writes a list of up to
60 consecutive links to the drive, starting at the defined sink
parameter.

PLC Block Transfer Instruction Data

PLC Message Write instruction length:

5-64 words

PLC Message Read instruction length:

5-64 words

Message Length

5-64

Header

Word 1

PLC Decimal Value

-32764

Header

Word 2

Header

Word 3

PLC Decimal Value

4 –– Message OK

-32764 –– Message Error

Data

Word 4

Number of Parameter

Links to Write

Number of Parameter

Links to Write

Data

Word 6

Data

Word 5

Status Number 1

Message Structure

Link Number 1

Link Number 2

Data

Word 6

Data

Word 5

Data

Word 4

Header

Word 3

Header

Word 2

Header

Word 1

0

Status Number 60

Data

Word 64

Status Number 2

Starting Parameter

Number

Parameter Number 1

Link Number 60

Data

Word 64

PLC Request –– PLC Message Write

Drive Response –– PLC Message Read

Message Operation

The Continuous Parameter Link Write function specified in the
PMW writes a set of consecutive links to the drive. Word 3 of the
PMW defines the number of links to be written. Word 4 defines the
starting sink parameter. The consecutive link source parameters are
then listed in the remaining header words. You can make up to 60
continuous links with this block transfer function.

Link Write

Continuous Parameter Link Write