Parameter write, Plc block transfer instruction data, Message operation – Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual

Page 60: Example, Parameter value write

Advertising
background image

4–18

Using Unscheduled Messaging

Publication 1336 FORCE–5.18 ––March, 1999

This message sent by the PLC Communications Adapter Board reads
the 16-bit parameter data value for the parameter number selected.

PLC Block Transfer Instruction Data

PLC MSG Write instruction length:

4 words

PLC MSG Read instruction length:

4 words

Message Length

4

Header

Word 1

Header

Word 1

PLC Decimal Value

-31999

Header

Word 2

Parameter Number

Data

Word 3

PLC Decimal Value

769 –– Message OK

Header

Word 2

Data

Word 3

Parameter Number

-31999 –– Message Error

Data

Word 4

Parameter Value

Data

Word 4

Message Structure

0

PLC Request –– PLC Message Write

Parameter Value or

Status Word

Drive Response –– PLC Message Read

Message Operation

The Parameter Value Write function specified in the PMW sends a
new value (specified in word 4 of the PMW header message) to the
parameter specified in the PMW header word 3. The value must be
in device units.

If an error has occurred:

Word 2 of the response returns a value of -31999.

Word 4 contains a status code.

Example

In this example, a value of 4096 was sent to parameter 20. 4096 is in
drive units and indicates a value of 100% of rated drive volts as
defined by parameter 147, Drive Rated Volts.

1

0

N7:10

2

3

4

5

6

7

8

9

N7:90

PLC MSG
Write File

PLC MSG
Read File

Data Format

20

4096

20

4096

4

0

-31999

769

➀ These values vary depending on parameters and products.

Parameter Write

Parameter Value Write