Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual

Page 92

Advertising
background image

4–50

Using Unscheduled Messaging

Publication 1336 FORCE–5.18 ––March, 1999

This field:

Indicates:

Seconds

The seconds and hundreths of seconds.

Date

The date of the month in Hex.

Day

The day of the week, where 1 is Sunday and 7 is
Saturday.

Year

The number of the year.1990 is referenced as 0.
Therefore, the year 1995 would return a value of 5.

Month

The month of the year, where 1 is January and 12 is
December.

If an error occurs in the block transfer, a value of -29952 is returned
in word 2 of the PMR response.

Example

In this example, the clock was read with a value of 2816 in word 2 of
the PMW. The PMR response indicated a successful read with a
value of 2816 in word 2.

Word 4 indicated a changing value for seconds.

The Hour value 0E indicates hour 14 of a 24 hour clock, or 2 pm.
The minute value 0A indicates 10, or 2:10 pm.

The Date of 17 in Hex is the 23

rd

and the 5

th

day of the week, or

Thursday.

The Year 05 is 1995.

The Month of 02 is February.

1

0

N7:10

2

3

4

5

6

7

8

9

N7:90

PLC MSG
Write File

PLC MSG
Read File

Data Format

0

0

7681

3

0

2816

2816

3594

5893

1282

N7:90

0E\01 0E\0A 17\05 05\02

S\..01S

Hr\Min Date\Day Yr\Mth

Real Time Clock Data Read

(continued)