Parameter read – Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual

Page 51

Advertising
background image

4–9

Using Unscheduled Messaging

Publication 1336 FORCE–5.18 ––March, 1999

This message is sent by the ControlNet Adapter Board and reads the
16-bit parameter data value for the parameter number selected.

PLC Block Transfer Instruction Data

PLC MSG Write instruction length:

3 words

PLC MSG Read instruction length:

4 words

Message Length

3

Header

Word 1

Header

Word 1

PLC Decimal Length

769

Parameter Number

PLC Decimal Value

769 –– Message OK

Parameter Value or

Status Word

Parameter Number

-31999 –– Message Error

Message Structure

Header

Word 2

Data

Word 3

Header

Word 2

Header

Word 3

Header

Word 4

0

PLC Request –– PLC Message Write

Drive Response –– PLC Message Read

Message Operation

The Parameter Value Read function specified in the PMW (PLC
MSG Write) reads a parameter value from the drive and places that
value (or an error code) in word 4 of the PMR (PLC MSG Read)
data file. The value shown is in device units.

If an error has occurred:

Word 2 of the PMR returns a value of -31999.

Word 4 contains the status code.

Parameter Read

Parameter Value Read