Parameters

Publication 1336 FORCE–5.18 ––March, 1999

456

Trend 1 Operand Parameter Y

[Tr1 Opnd Parm Y]

Tr1 Opnd Parm Y specifies the second of two
parameter numbers used for the trend trigger
evaluation. The data value for the entered link
parameter number is used in the trigger evaluation.

Parameter Number

456

Parameter Type

Read/Write, Sink

Display Units / Drive Units

Dependent on Link➀

Factory Default

0

Minimum Value

–32767➀

Maximum Value

+32767➀

File – Group

Diagnostics – Trend Setup

➀ These values depend on the source parameter that this parameter is linked to.
For example, if the source parameter’s drive units are rpm, then Tr1 Opnd Parm Y’s
drive units will be displayed in rpm. The minimum and maximum values are also
link dependent.

457

Trend 1 Operator

[Tr1 Operator]

Tr 1 Operator specifies the operator used for the
trend trigger evaluation. The available operators
are:

Value

Description

1

Greater Than

(.GT.)

2

Less Than

(.LT.)

3

Equals

(.EQ.)

4

Not Equals

(.NE.)

5

Logical AND

(.AND.)

6

Logical NAND (.NAND.)

7

Logical OR

(.OR.)

8

Logical NOR

(.NOR.)

Parameter Number

457

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

None

Factory Default

5

Minimum Value

1

Maximum Value

8

File – Group

Diagnostics – Trend Setup

458

Trend 1 Sample Rate

[Tr1 Sample Rate]

Tr1 Sample Rate specifies the interval at which the
data in the Trend In 1 parameter is sampled. It is
programmable in 2 millisecond increments. All
values are rounded down to the nearest 2
millisecond interval.

Parameter Number

458

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

Seconds

Factory Default

0.020 Seconds

Minimum Value

0.002 Seconds

Maximum Value

30 Seconds

File – Group

Diagnostics – Trend Setup

459

Trend 1 Post Samples

[Tr1 Post Samples]

Tr1 Post Samples specifies the number of data
samples to be gathered once the trigger evaluation
becomes true. There is always a sample reserved
for the instance when the trigger condition becomes
true.

Parameter Number

459

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

None

Factory Default

15

Minimum Value

0

Maximum Value

499

File – Group

Diagnostics – Trend Setup