Message operation, Example, Parameter read full – Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual

Page 58

Advertising
background image

4–16

Using Unscheduled Messaging

Publication 1336 FORCE–5.18 ––March, 1999

Data

Word 15

Parameter Text

Character 12

Character 11

Parameter Text

Character 14

Character 13

Parameter Text

Character 16

Character 15

File, Group, Element

Minimum Value

Maximum Value

Default Value

Unit Text

Character 2

Character 1

Unit Text

Character 4

Character 3

Data

Word 16

Data

Word 17

Data

Word 18

Data

Word 19

Data

Word 20

Data

Word 21

Data

Word 22

Data

Word 23

Drive Response –– PLC Message Read

Message Operation

The Parameter Read Full function specified in the PMW retrieves the
attributes of the requested parameter. The attributes for each
parameter include the data, minimum and maximum values, and the
parameter text. The response message returns this information,
beginning with data word 4. The parameter text is returned with each
data word containing two ASCII characters per word. This data
returns with the first and second characters in opposite order as
shown in the following example.

If an error has occurred in the block transfer, word 2 of the PMR
returns a value of -32000.

Example

In this example, a Parameter Read Full was performed through block
transfer on a 1336

FORCE. N7:10 shows the header message for the

PMW. The data is returned in the PMR data file, starting with word
4, for parameter 101. Word 4 shows the present value in drive units.
Words 5 through 9 provide scaling information, used to convert drive
units to engineering units. Words 10 through 17 provide the
parameter name.

Parameter Read Full

(continued)