Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual

Page 171

Advertising
background image

6–29

Parameters

Publication 1336 FORCE–5.18 ––March, 1999

400

Analog Output 1 Offset

[Analog Out 1 Offset]

Analog Out 1 Offset determines the offset applied to
the Analog Out 1 value after the scale factor is
applied. This allows you to shift the range of the
analog output.

Parameter Number

400

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

±

4096

Factory Default

0

Minimum Value

–20 Volts

Maximum Value

+20 Volts

File – Group

Communications I/O – Analog Output

401

Analog Output 1 Scale

[Analog Out 1 Scale]

Analog Out 1 Scale determines the scale factor or
gain for the Analog In 1 value. A +2048 value
corresponds to a +10V output signal at TB21. The
value sent (linked) to Analog Out 1 is scaled by the
corresponding scale parameter before it is offset and
converted to an analog signal.

Scale Factor

Drive Units

1

32767

1/2

16383

1/4

8192

1/16

2048

Parameter Number

401

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

±

32767

Factory Default

+1

Minimum Value

–1

Maximum Value

+1

File – Group

Communication I/O – Analog Output

402

Analog Output 2 Offset

[Analog Out 2 Offset]

Analog Out 2 Offset determines the offset applied to
the Analog Out 2 value after the scale factor is
applied. This allows you to shift the range of the
analog output.

Parameter Number

402

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

±

4096

Factory Default

0

Minimum Value

–20 Volts

Maximum Value

+20 Volts

File – Group

Communications I/O – Analog Output

403

Analog Output 2 Scale

[Analog Out 2 Scale]

Analog Out 2 Scale determines the scale factor or
gain for the Analog In 2 value. A +2048 value
corresponds to a +10V output signal at TB21. The
value sent (linked) to Analog Out 2 is scaled by the
corresponding scale parameter before it is offset and
converted to an analog signal.

Scale Factor

Drive Units

1

32767

1/2

16383

1/4

8192

1/16

2048

Parameter Number

403

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

±

32767

Factory Default

+1

Minimum Value

–1

Maximum Value

+1

File – Group

Communication I/O – Analog Output

Advertising