6–38

Parameters

Publication 1336 FORCE–5.18 ––March, 1999

460

Trend 1 Continuous Trigger

[Tr1 Cont Trigger]

Tr1 Cont Trigger specifies the type of trend. You can
choose either 0 for one–shot or 1 for continuous.

With a one–shot trend, once the trigger condition is
true and the number of samples after the trigger is
taken are gathered, the trend stops.

With a continuous trend, once the trigger condition is
true and the number of samples after the trigger is
taken are gathered, the trend continues looking for
the next occurrence of a true trigger condition.

Parameter Number

460

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

None

Factory Default

0

Minimum Value

0

Maximum Value

1

File – Group

Diagnostics – Trend Setup

461

Trend 1 Select

[Tr1 Select]

Tr1 Select specifies the trend mode. The states are
as follows:

0

Disable the trend.

1

Enable the trend.

2

Force a true trigger condition.

Parameter Number

461

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

None

Factory Default

0

Minimum Value

0

Maximum Value

2

File – Group

Diagnostics – Trend Setup

Enums

0 = Disable

1 = Enable

2 = Force Trig

462

Trend 1 Status

[Tr1 Status]

Tr1 Status identifies which state the trend is
currently in. The following states are possible:

1 Stopped

Trending is not executing.

2 Running

Trending is executing, but the trigger
point has not yet been reached.

3 Tripped/Trigger Trending is executing, and the trigger

point has been reached.

4 Tripped/Forced The trigger point was forced.

Parameter Number

462

Parameter Type

Read Only, Non–Linkable Source

Display Units / Drive Units

None

Factory Default

1

Minimum Value

1

Maximum Value

4

File – Group

Diagnostics – Trend I/O

Enums

1 = Stopped

2 = Running

3 = Trip Trig

4 = Force Trip

463

Trend Output 1

[Trend Out 1]

Trend Out 1 displays the latest 500 trend input data
values once the trigger condition is true and all post
samples are gathered. This parameter is updated at
the same rate as the data was sampled. This
parameter can be linked to Analog Output (for
example) and a chart recorder connected to Analog
Output to provide a hard copy of the trend data.

Parameter Number

463

Parameter Type

Read Only, Source

Display Units / Drive Units

None

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

File – Group

Diagnostics – Trend I/O