Time stamp, Plc block transfer instruction data, Message operation – Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual

Page 98: Reference time stamp data read

Advertising
background image

4–56

Using Unscheduled Messaging

Publication 1336 FORCE–5.18 ––March, 1999

The Reference Time Stamp Data Read message reads the reference
time stamp value from the drive.

PLC Block Transfer Instruction Data

PLC Message Write instruction length:

3 words

PLC Message Read instruction length:

7 words

Header

Word 1

Header

Word 1

Header

Word 2

Header

Word 2

Header

Word 3

0

Message Structure

Message Length

3

Header

Word 3

Reference Number

PLC Decimal Value

2816

Clock Time

Seconds

10ths of MS

Clock Time

Hour

Minute

PLC Decimal Value

2816 –– Message OK

-29952 –– Message Error

Clock Time

Date

Day

Clock Time

Year

Month

Data

Word 4

Data

Word 5

Data

Word 6

Data

Word 7

0

PLC Request –– PLC Message Write

Drive Response –– PLC Message Read

Message Operation

You can define the reference time stamp to monitor the time of a
specific event. This function allows this time to be read from the
device. The time stamp is returned in the order shown in the header
message. This information should be viewed as ASCII text.

The Time is based on a 24-hour clock.

This field:

Indicates:

Seconds

The seconds and tenths of milliseconds.

Date

The date of the month in ASCII.

Day

The day of the week, where 1 is Sunday and 7 is
Saturday.

Year

The number of the year. 1990 is referenced as 0.
Therefore, the year 1995 would return a value of 5.

Month

The month of the year, where 1 is January and 12 is
December.

Time Stamp

Reference Time Stamp Data
Read