background image

4–55

Using Unscheduled Messaging

Publication 1336 FORCE–5.18 ––March, 1999

The Clear Run Time Accumulator message provides a way of
clearing the run time accumulator data stored in the drive.

PLC Block Transfer Instruction Data

PLC Message Write instruction length:

3 words

PLC Message Read instruction length:

3 words

Header

Word 1

Header

Word 1

Header

Word 2

Header

Word 2

Header

Word 3

0

Message Structure

Message Length

3

Header

Word 3

0

PLC Decimal Value

-29950

PLC Decimal Value

2818 –– Message OK

-29950 –– Message Error

Message Length

3

PLC Request –– PLC Message Write

Drive Response –– PLC Message Read

Message Operation

The Clear Run Time Accumulator defines a value of -29950 in the
PMW. Word 2 can clear the accumulated run time stored in the
drive. This allows you to monitor an accumulated time based on a
specific event.

Example

This function was requested to clear the accumulated run time in the
drive since the last scheduled maintenance downtime. In this
example, the PMW requested a clear with a value of -29950 in word
2. The PMR response indicated a successful clear by returning a
value of 2818 in word 20 of the PMR header message.