Link write, Plc block transfer instruction data, Message operation – Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual

Page 86: Example, Parameter link clear

Advertising
background image

4–44

Using Unscheduled Messaging

Publication 1336 FORCE–5.18 ––March, 1999

The Parameter Link Clear message deletes all user–configured
parameter links in the drive.

PLC Block Transfer Instruction Data

PLC Message Write instruction length:

4 words

PLC Message Read instruction length:

3 words

Message Length

4

Header

Word 1

Header

Word 1

PLC Decimal Value

-30464

Header

Word 2

Header

Word 3

Header

Word 2

Header

Word 3

0

1

Data

Word 4

PLC Decimal Value

2304 –– Message OK

0

-30464 –– Message Error

0

Message Structure

PLC Request –– PLC Message Write

Drive Response –– PLC Message Read

Message Operation

When this request is sent to the drive, all drive parameter links that
you configured are deleted.

If an error has occurred, word 2 of the PMR returns -30464.

Example

In this example, a Parameter Link Clear request was sent through the
PMW. The PMR was only required to check for an error.

1

0

N7:0

2

3

4

5

6

7

8

9

N7:90

PLC MSG
Write File

PLC MSG
Read File

Data Format

0

1

0

4

0

-30464

2304

Link Write

Parameter Link Clear

Advertising