Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual

Page 181

Advertising
background image

6–39

Parameters

Publication 1336 FORCE–5.18 ––March, 1999

464

Trend Input 2

[Trend In 2]

Trend In 2 specifies the data value to sample at the
specified trend sample rate. You should link Trend
In 2 to a source parameter (such as velocity, torque,
or current) for the trend to make sense.

Parameter Number

464

Parameter Type

Read/Write, Sink

Display Units / Drive Units

Dependent on Link➀

Factory Default

0

Minimum Value

–32767➀

Maximum Value

+32767➀

File – Group

Diagnostics – Trend I/O

➀ These values depend on the source parameter that this parameter is linked to.
For example, if the source parameter’s drive units are rpm, then Trend In 2’s drive
units will be displayed in rpm. The minimum and maximum values are also link
dependent.

465

Trend 2 Operand Parameter X

[Tr2 Opnd Parm X]

Tr2 Opnd Parm X specifies the first of two parameter
numbers for the trend trigger evaluation. The data
value for the entered link parameter number is used
in the trigger evaluation.

Parameter Number

465

Parameter Type

Read/Write, Sink

Display Units / Drive Units

Dependent on Link➀

Factory Default

0

Minimum Value

–32767➀

Maximum Value

+32767➀

File – Group

Diagnostics – Trend Setup

➀ These values depend on the source parameter that this parameter is linked to.
For example, if the source parameter’s drive units are rpm, then Tr2 Opnd Parm X’s
drive units will be displayed in rpm. The minimum and maximum values are also
link dependent.

466

Trend 2 Operand Parameter Y

[Tr2 Opnd Parm Y]

Tr2 Opnd Parm Y specifies the second of two
parameter numbers used for the trend trigger
evaluation. The data value for the entered link
parameter number is used in the trigger evaluation.

Parameter Number

466

Parameter Type

Read/Write, Sink

Display Units / Drive Units

Dependent on Link➀

Factory Default

0

Minimum Value

–32767➀

Maximum Value

+32767➀

File – Group

Diagnostics – Trend Setup

➀ These values depend on the source parameter that this parameter is linked to.
For example, if the source parameter’s drive units are rpm, then Tr2 Opnd Parm Y’s
drive units will be displayed in rpm. The minimum and maximum values are also
link dependent.

467

Trend 2 Operator

[Tr2 Operator]

Tr2 Operator specifies the operator used for the
trend trigger evaluation. The available operators
are:

Value

Description

1

Greater Than

(.GT.)

2

Less Than

(.LT.)

3

Equals

(.EQ.)

4

Not Equals

(.NE.)

5

Logical AND

(.AND.)

6

Logical NAND (.NAND.)

7

Logical OR

(.OR.)

8

Logical NOR

(.NOR.)

Parameter Number

467

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

None

Factory Default

5

Minimum Value

1

Maximum Value

8

File – Group

Diagnostics – Trend Setup

Advertising