1–2

Installing and Wiring Your ControlNet Adapter Board

Publication 1336 FORCE–5.18 ––March, 1999

To mount your ControlNet Adapter Board on to your 1336 FORCE,
you need to:

!

ATTENTION: To avoid a shock hazard, assure that
all power to the drive has been removed before
proceeding.

1. Place the CNA Board over the keyed mounting slots.

2. Slide the board up into the main control board connector J1.

3. Secure the board to the 1336 FORCE mounting plate using the

two Phillips-head screws that are provided with the kit.

4. Connect primary and redundant ControlNet channels at the fiber

optic connector. You must maintain a minimum bend radius on
the fiber optic cable of 1 inch at all times. If you cannot maintain
this bend radius, remove the plastic strain relief following the
instructions for Frame D drives detailed on page 1-8. Using the
ControlNet Adapter Board on a Frame D drive, always requires
the removal of the cable strain relief. See page 1-8 for special
cable instructions for D Frame drives.

Mounting the ControlNet
Adapter Board