Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual

Page 192

Advertising
background image

7–4

Troubleshooting

Publication 1336 FORCE–5.18 ––March, 1999

Primary Channel Status D8, D10, and D12
Redundant Channel Status D13, D14, and D15

These LEDs reflect the operational status of ControlNet
communications.

LED:

State:

ControlNet Adapter Function:

D8 and D13
(Red)

LED on

Hardware malfunction

LED off

Communications loss or D12 and D15
on.

LED
blinking

A PLC has the rack inhibited or the
PLC is in Reset/Program/Test mode

D10 and
D14

LED on

Malfunction

(Yellow)

LED off

Malfunction

LED
blinking

Operational

D12 and
D15

LED on

Normal PLC controller
communications

(Green)

LED off

No communications to PLC control or
D8 and D13 on

LED
blinking

PLC in Reset/Program/Test mode or
PLC has rack inhibited

Advertising