Rockwell Automation 1336T ControlNet Frn1.02 Rev 1.5 User Manual

Page 169

Advertising
background image

6–27

Parameters

Publication 1336 FORCE–5.18 ––March, 1999

392

Analog Input 1 Offset

[Analog In 1 Offset]

Analog In 1 Offset determines the offset applied to
the raw Analog In 1 values before the scale factor is
applied. This allows you to shift the range of the
analog input.

Parameter Number

392

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

±

4096

Factory Default

0

Minimum Value

–20 Volts

Maximum Value

+20 Volts

File – Group

Communications I/O – Analog Input

393

Analog Input 1 Scale

[Analog In 1 Scale]

Analog In 1 Scale determines the scale factor or
gain for the Analog In 1 value. A +10V dc signal
applied to Analog In 1 at TB21 is converted to a
+2048 digital value used by the 1336 FORCE.
Before the digital value is displayed or transferred to
the drive, the scale factor is applied allowing an
effective digital range of

±

32767 (16 x 2048). The

absolute digital value is clamped at 32767.

Scale Factor

Drive Units

1

2048

2

4096

4

8192

16

32767

Parameter Number

393

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

±

32767

Factory Default

+1

Minimum Value

–16

Maximum Value

+16

File – Group

Communications I/O – Analog Input

394

Analog Input 2 Offset

[Analog In 2 Offset]

Analog In 2 Offset determines the offset applied to
the raw Analog In 2 values before the scale factor is
applied. This allows you to shift the range of the
analog input.

Parameter Number

394

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

±

4096

Factory Default

0

Minimum Value

–20 Volts

Maximum Value

+20 Volts

File – Group

Communications I/O – Analog Input

395

Analog Input 2 Scale

[Analog In 2 Scale]

Analog In 2 Scale determines the scale factor or
gain for the Analog In 2 value. A +10V dc signal
applied to Analog In 2 at TB21 is converted to a
+2048 digital value used by the 1336 FORCE.
Before the digital value is displayed or transferred to
the drive, the scale factor is applied allowing an
effective digital range of

±

32767 (16 x 2048). The

absolute digital value is clamped at 32767.

Scale Factor

Drive Units

1

2048

2

4096

4

8192

16

32767

Parameter Number

395

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

±

32767

Factory Default

+1

Minimum Value

–16

Maximum Value

+16

File – Group

Communications I/O – Analog Input

Advertising