Chapter

2

Publication 1336 FORCE–5.18 ––March, 1999

Starting Up

Chapter 2 provides the following information:

setting the DIP switch to configure the Primary and Redundant
channels

setting up the analog I/O

a description of the SCANport capabilities

a description of the pre-configured links

The ControlNet Adapter Board contains four address switches .
Only switch U3 is used on the CNA board to set the Node Address.
Switches U2, U4 and U5 are NOT used in this application. Changes
to switch settings will not take effect until power is re-applied.

!

ATTENTION: Use a blunt, pointed instrument (such
as a ball point pen) to set DIP switches. Do not use a
pencil. Pencil lead (graphite) may damage switch
assemblies.

!

ATTENTION: The CNA Board uses both input and
output image table words for drive control. The CNA
Board is not compatible with complementary I/O
configurations. Failure to check connections and
switch settings for application compatibility when
configuring the CNA Board could result in personal
injury and /or equipment damage due to unintended or
undesirable drive or process equipment operation.

If you encounter any operating faults once switch settings have been
applied, refer to Chapter 7, Troubleshooting.

NOTE: DIP Switch orientation on the CNA board is as follows:

CLOSED = “ON” = “1”
OPEN = “OFF” = “0”

ON ON Off Off

Open

Closed

Chapter Objectives

Setting the DIP Switches

"