Using Unscheduled Messaging

Publication 1336 FORCE–5.18 ––March, 1999

The Continuous Parameter Value Read function reads a continuous
list of parameters beginning with the starting parameter number.
You define the number of parameters to be read.

PLC Block Transfer Instruction Data

PLC MSG Write instruction length:

4 words

PLC MSG Read instruction length:

5-64 words

Message Length

4

Header

Word 1

Header

Word 1

PLC Decimal Value

1

PLC Decimal Value

1 –– Message OK

-32767 –– Message Error

Number of Parameter

Values to Read

Starting Parameter

Number

Number of Parameter

Values to Read

Starting Parameter

Number

Data

Word 64

Message Structure

Header

Word 2

Data

Word 3

Data

Word 4

Header

Word 2

Data

Word 3

Data

Word 4

Data

Word 5

Data

Word 6

Data

Word 7

Value Number 1 or

Status Word

Value Number 2 or

Status Word

Value Number 3 or

Status Word

Value Number 60 or

Status Word

0

PLC Request –– PLC Message Write

Drive Response –– PLC Message Read

Message Operation

The Continuous Parameter Value Read function specified in the
PMW reads a consecutive group of parameter values from the
device, beginning with the starting parameter number defined in
word 4 of the PMW message. Word 3 of the PMW message defines
the number of parameters to be read. The values return in the PMR
response, beginning with word 5 of the message.

If an error has occurred in reading any of the values, the PMR
returns a status word with a negative value instead of the parameter
value.

Parameter Read

Continuous Parameter Value
Read