Troubleshooting

Publication 1336 FORCE–5.18 ––March, 1999

Fault text and

code:

Suggested action:

Description:

Fault

type:

Class 3 Timeout
36023

Soft/
Warning?
None

Drive timed out on scheduled
control data reception from a
device.

Check connections & cables. Check
that all devices that are configured on
the network have a clas 3 connection to
the drive operational. Check
programming within the PLC or any
other device with a class 3 connection
to the drive. Check for general errors
occurring on the network. Check that
the network was not being
reconfigured.

Plug Failure
36024

Hard

Internal Fault detected

Check version of Adapter Board for
compatibility with Main board. If
condition persists, replace adapter
board.