Using Unscheduled Messaging

Publication 1336 FORCE–5.18 ––March, 1999

Message Operation

The Fault Queue Entry Read Full function specified in the PMW
reads the contents of the fault queue for the input entry number
specified in word 3 of the PMW message. The response returns the
fault text which you can view as ASCII text. The text will have
every two characters in reverse order and return a time stamp,
indicating the day and time the fault occurred. The Clock Time is
returned in the order shown in the header message. You should view
this information as ASCII text.

This field:

Indicates:

Reference

am or pm, where 0 is am and 1 is pm.

Date

The date of the month in ASCII.

Day

The day of the week, where 1 is Sunday and 7 is
Saturday.

Year

The number of the year. 1990 is referenced as 0.
Therefore, the year 1995 would return a value of 5.

Month

The month of the year, where 1 is January and 12
is December.

If an error has occurred, word 2 of the response returns a negative
value.

Example

In this example, Fault Queue Entry #3 was retrieved from the drive.
The PMR response returned the ASCII text Drive Reset Flt, with
each two characters reversed. The Fault Code for this example is 22.

1

0

N7:10

2

3

4

5

6

7

8

9

N7:30

PLC MSG
Write File

PLC MSG
Read File

Data Format

3

3

29252

3

0

1792

1792

30313 8293 25938 25971 8308 27718

N7:100

7681

3594

8308

22

5893

1282

N7:90

03\00

r D

0

07\00

V i

e

e R

e s

t

l F

N7:100

1E\01 0E\0A

t

00\16

17\05 05\02

These values vary depending on parameters and products.

ASCII Display Values

Fault Entry Read Full

(continued)