Draw a Circuit Diagram with Pico 4-41

Parameter Display and Parameter Set for the High-Speed Counter

In the parameter display of a counter relay you change the mode, the
setpoint and the enable of the parameter display.

Value Range

The counter relay is in Run mode.

Behavior When Value Range is Reached

The Pico control relay is in Run mode.

The value is retained if the counter reaches 32000. If the counter
counts down and reaches 0, this value is retained.

Parameter display in Run mode:

Retention

The high-speed counter can be run with the retentive actual value.
You can select the retentive counter relays in the System menu by
selecting Retention. C5 to C7, C8 and C13 to C16 can be selected.

If a counter relay is retentive, the actual value is retained when the
operating mode changes from Run to Stop as well as when the power
supply is switched off.

C13

Counter function relay number 13.

H

H - High-speed counter mode.

+

• + appears in the Parameter menu.
• - does not appear in the Parameter

menu.

S

Setpoint, constant from 00000 to 32000.

C13 H +

00950

S

C13 H +

00200

C:00877

S

Current setpoint, constant

Contact has not switched.
Contact has switched. Actual value (0153)