Rockwell Automation 1760-xxxx Pico Controller User Manual User Manual
Page 172
Publication 1760-UM001D-EN-P - September 2005
8-4 Inside Pico
Example: Parallel Circuit
Calculate the maximum cycle time for the
following circuit diagram:
Example: Circuit with Branches
Function
Number
Time Duration
in µs
Total
Basic pulse
1
210
210
Refresh
1
3500
3500
Contacts and bridged contact fields
4
20
80
Coils
1
20
20
Total rungs from the first one to the last
one, with empty ones in between
2
50
100
Connecting lines (only
)
–
20
–
Timing relays
–
–
–
Counters
–
–
–
Analog value function relays
–
–
–
Total
3910
Function
Number
Time Duration
in µs
Total
Basic pulse
1
210
210
Refresh
1
3500
3500
Contacts and bridged contact fields
9
20
180
Coils
4
20
80
Total rungs from the first one to the last
one, with empty ones in between
4
50
200
Connecting lines (only
)
3
20
60
Timing relays
2
40
40
I2----------{Q4
I3
,
,
I1---------TT1
T1------{Q1
T1------TT2
T2------{Q2
,
,