8-4 Inside Pico

Example: Parallel Circuit

Calculate the maximum cycle time for the
following circuit diagram:

Example: Circuit with Branches

Function

Number

Time Duration
in µs

Total

Basic pulse

1

210

210

Refresh

1

3500

3500

Contacts and bridged contact fields

4

20

80

Coils

1

20

20

Total rungs from the first one to the last
one, with empty ones in between

2

50

100

Connecting lines (only

)

20

Timing relays

Counters

Analog value function relays

Total

3910

Function

Number

Time Duration
in µs

Total

Basic pulse

1

210

210

Refresh

1

3500

3500

Contacts and bridged contact fields

9

20

180

Coils

4

20

80

Total rungs from the first one to the last
one, with empty ones in between

4

50

200

Connecting lines (only

)

3

20

60

Timing relays

2

40

40

I2----------{Q4

I3

,

,

I1---------TT1

T1------{Q1

T1------TT2

T2------{Q2

,

,