4-38 Draw a Circuit Diagram with Pico

Parameter Display and Parameter Set for Frequency Counter

In the parameter display of a counter relay you change the mode, the
setpoint and the enable of the parameter display.

Value Range

The counter relay counts between 4 and 1000 (Hz).

Parameter display in Run mode:

Retention

Setting retention on the frequency counter serves no purpose since
the frequency is continuously measured.

IMPORTANT

The frequency counter can also be enabled
specifically for a special operating state. This has the
advantage that the cycle time of the device is only
burdened with the frequency measurement when it
is taking place. If the frequency counter is not
enabled, the cycle time of the device is shorter.

C15

Counter function relay number 15

F

Mode F: frequency counter

+

• + appears in the Parameter menu.
• - does not appear in Parameter menu.

S

Setpoint, constant from 00000 to 01000 (32000 is a possible setting, the
maximum frequency is 1 kHz).

C15 F +

00200

S

C15 F +

00200

C:00153

S

Current setpoint, constant

Contact has not switched.
Contact has switched. Actual value (0153)