10 - troubleshoot your controller, Messages from the pico system, Chapter 10 – Rockwell Automation 1760-xxxx Pico Controller User Manual User Manual

Page 185: Troubleshoot your controller, Messages from the pico system -1, Chapter

Advertising
background image

1

Publication 1760-UM001D-EN-P - September 2005

Chapter

10

Troubleshoot Your Controller

You may sometimes find that Pico does not do exactly what you
expect. If this happens, read through the following notes which are
intended to help you solve some of the problems you may encounter.

Use the power flow display in Pico to check the logic operations in
the Pico circuit diagrams with reference to the switching states of
contacts and relays.

Only qualified persons should test Pico voltages while the device is in
operation.

Messages from the Pico
System

Pico System Messages on
the LCD

Explanation

Remedy

No display

Power interrupted

Turn on the power.

Pico LCD faulty

Replace the Pico.

Continuous display

TEST: AC

Self-test aborted

Replace the Pico.

TEST: EEPROM

TEST: DISPLAY

TEST: CLOCK

ERROR: I2C

Memory module removed or not
inserted correctly before saving

Insert the memory
module.

Memory module faulty

Replace the memory
module.

Pico is faulty

Replace the Pico.

ERROR: EEPROM

The memory for storing the
retentive values or the Pico circuit
diagram memory is faulty.

Replace the Pico.

ERROR: CLOCK

Clock error

Replace the Pico.

ERROR: LCD

LCD is faulty

Replace the Pico.

ERROR: ACLOW

Incorrect ac voltage

Test the voltage.

Pico is faulty

Replace the Pico.

Advertising