Publication 1760-UM001D-EN-P - September 2005

Draw a Circuit Diagram with Pico 4-35

Parameters for Counters

The parameter display for counters is used to change the counter
setpoint value and to enable or disable parameter access.

The symbol ‘

{

‘ before DIR, CNT and RES indicates whether the coil

function is programmed in the circuit diagram.

The actual value is only displayed in Run mode. The parameter
display can then be called via the power flow display or via the
PARAMETER option from the main menu.

The coil symbol is not displayed if you select the parameter display
via the PARAMETER menu option.

The counter relay counts between 0 and 32000.

When the Pico is in Run mode and the value of 32000 is reached, this
value is retained until the count direction is changed. If the value of

C2

Counter function relay number 2

N

• Mode N: up/down counter
• Mode H: high-speed up/down counter
• Mode F: frequency counter

+

• + appears in the Parameter menu
• - does not appear in the Parameter

menu.

S

Setpoint, constant from 00000 to 32000

Parameter

Coil Function

Meaning

DIR

DC1 to DC16

Counting direction

Coil not triggered: count up
Coil triggered: count down

CNT

CC1 to CC16

Counting pulse

RES

RC1 to RC16

Reset, coil triggered: actual value reset to
00000

Parameters Displayed via the PARAMETER Menu Option

+

Access enabled

-

Access disabled

C2 N +

00.000

S