Publication 1760-UM001D-EN-P - September 2005

Installation 2-17

To limit the current to 400 mA, connect a 1K

Ω resistor in series

upstream from the circuit as shown.

.

Connect 24 V dc Inputs

Use input terminals I1 to I8 (or I12 for 18-point Pico) to connect
push-buttons, switches, or 3- or 4-wire proximity switches. Given the
high off-state leakage current, do not use 2-wire proximity switches.

Example Using 1760-L12BWB-xx

Input

Specification

Input Signal Voltage Range

OFF signal: 0 to 5V dc

ON signal: 15V to 28.8V dc

Input Current

I1 to I6, I9 to I12, R1 to R12: 3.3 mA at 24V dc

I7 and I8: 2.2 mA at 24V dc

L1

1A

L2

L1

L2

I2

I3

I4

I5

I6

I7

I8

I1

100 to 240V ac

50/60Hz

Inputs x 100 to 240V ac

100 nF, 275V ac capacitor

1K

0.25W
resistor

24V dc

+24 V COM

I2

I3

I4

I5

I6

I7

I8

I1

Inputs x 24V dc (I7,I8 0 to 10V)

+24V

0V

1A