Electrical specifications – Rockwell Automation 1760-xxxx Pico Controller User Manual User Manual

Page 192

Advertising
background image

Publication 1760-UM001D-EN-P - September 2005

A-2 Specifications

Electrical Specifications

Ambient mechanical conditions

Specification

Value

Standard

Pollution degree

2

Protection class

IP 20

EN 50178, IEC 60529, VBG4

Vibration

10 to 57 Hz
(constant amplitude 0.15
mm)

IEC 60068-2-6

57 to 150 Hz
(constant acceleration 2G)

Shock

18 shocks
(semi-sinusoidal 15G/11 ms)

IEC 60068-2-27

Drop

50 mm (1.97 in)

IEC 60068-2-31

Drop, packaged

1m (39.4 in)

IEC 60068-2-32

Electromagnetic compatibility (EMC)

Electrostatic discharge

8 KV air discharge,
6 KV contact discharge

IEC/EN 61000-4-2,
severity level 3

Electromagnetic fields

Field strength 10 V/m

IEC/EN 61000-4-3

Emitted interference,
interference immunity

Class B

EN 55011, EN 55022

Fast Transient Burst

2 KV power supply
2 KV signal cables

IEC/EN 61000-4-4,
severity level 3

High-energy pulses (surge)
Pico 1760-LxxAWA
1760-IA12XOW6I

2 KV power cable
symmetrical

IEC/EN 61000-4-5

High-energy pulses (surge)
Pico 1760-LxxBWB-xx
1760-IB12X0B8

0.5 KV power cable
symmetrical

IEC/EN 61000-4-5,
severity level 2

Line Conducted
Interference

10V

IEC/EN 61000-4-6

Dielectric strength

Clearance and creepage
distances

EN 50178, UL 508, CSA C22.2, No 142

Dielectric strength

EN 50178

Backup/accuracy of real-time clock (except ‘-NC’)

Clock capacitor back-up

at 25°C (77°F)

Nominal 64 hours

at 40°C (104°F)

Nominal 24 hours

Accuracy of the real-time
clock

Nominal ±5s/day, ± 0.5 h/year

Repetition accuracy of timing relays

Accuracy of timing relays

±1% of value

Advertising