Publication 1760-UM001D-EN-P - September 2005

Draw a Circuit Diagram with Pico 4-29

Typically, delay times are >40 ms for the 1760-L12xxx and >80 ms for
the 1760-L18xxx. This is because a time value less than the maximum
scan time of the Pico controllers may cause uncontrolled switching
states.

Timing Relays, On-Delay, Without and With Random Switching

The relay switches a contact after the setpoint delay has elapsed. With
random switching, the relay contact switches randomly at any time up
to the specified time value (shown shaded in figure).

Timing Diagram

Time Units and Setpoint Time Parameters

Resolution

S 00.00

Seconds 10 x milliseconds, 00.00 to 99.99

10 ms

M:S 00:00

Minutes: seconds, 00:00 to 99:59

1 s

H:M 00:00

Hours: minutes, 00:00 to 99:59

1 min.

Parameter Set Displayed via the PARAMETER Menu Option

+

Access enabled

-

Access disabled

X

Switch with on-delay

Switch with on-delay and random time range

Switch with off-delay

Switch with off-delay and random time range

Switch with single-pulse

Switch with flashing

?X

X

Switch Function
Parameters

Description

X

?X

t

t

t

A

B

C

Output

Reset

Trigger

On

On

On