9-2 Use of Expansion Modules

Outputs

Expansion module outputs are processed as relay coils or contacts in
the same way as they are on the Pico controller. The expansion
output relays are numbered S1 to S8.

Expansion module 1760-IA12XOW6I provides 6 relay outputs. The
other outputs, S7 and S8, can be used as markers.

Expansion module 1760-IB12XOB8 provides 8 transistor outputs. See
Monitor for Short Circuit or Overload on page 9-4 for information on
output faults.

Operation

How the Expansion Module is Recognized

When at least one R contact or S contact/coil is used in the circuit
diagram, the Pico controller assumes that an expansion module is
connected.

Data Transfer Behavior

The input and output data of the expansion module is transferred
serially in both directions. Take into account the modified reaction
times of the inputs and outputs when using expansion modules.

Input and Output Reaction Times of Expansion Modules

TIP

The debounce setting has no effect on expansion
modules.

Transfer Times for Input and Output Signals

Input or Output

Reaction Time

R1 to R12

30 ms + one cycle

S1 to S6 (or S8)

15 ms + one cycle time