Outputs

Relay Outputs

Specification

1760-L12AWA
1760-L12AWA-NC
1760-L12AWA-ND
1760-L12BWB
1760-L12BWB-NC
1760-L12BWB-ND
1760-L12DWD
1760-L12DWD-ND
1760-L12NWN
1760-L12NWN-ND

1760-L18AWA
1760-L18AWA-EX
1760-L18AWA-EXND
1760-L18BWB-EX
1760-L18BWB-EXND
1760-L18DWD-EX
1760-L18DWD-EXND
1760-L18NWN-EX
1760-L18NWN-EXND
1760-IA12XOW6I
1760-IB12XOW6I
1760-OW2

Number of Relay Outputs

4

6 (2 for 1760-OW2)

In Groups of

1 (2 for 1760-OW2)

Connection of Outputs in Parallel to Increase
the Output

Not permissible

Protection for an Output Relay

Miniature circuit-breaker B16 or 8 A fuse (slow)

Isolation to Power Supply and Inputs

300V ac reinforced insulation

Contacts Relays

Conventional Thermal Current

8 A (10 A UL)

Recommended for Load

> 500 mA, 12V ac/dc

Short-Circuit Resistance COS 1

16 A characteristic B (B16) at 600 A

Short-Circuit Resistance COS 0.5 to 0.7 16 A characteristic B (B16) at 900 A

Rated Impulse Withstand Voltage U

imp

Contact/Coil

6 KV

Rated Insulation Voltage U

i

Rated Operational Voltage U

e

250V ac

Isolation to EN 50178 Between Coil
and Contact

300V ac reinforced insulation

Isolation to EN 50178 Between Two
Contacts

300V ac reinforced insulation

Making Capacity

AC-15 COS

φ = 0.4, 250V ac, 3A (600

Ops/h)

300,000 switching operations

DC-13 L/R

≤ 150 ms, 24V dc, 1A (500

Ops/h)

200,000 switching operations

Breaking Capacity

AC-15 COS

φ = 0.7 250V ac, 3 A (600

Ops/h)

300,000 switching operations

DC-13 L/R

≤ 150 ms 24V DC, 1 A (500

Ops/h)

200,000 switching operations