10-2 Troubleshoot Your Controller

Possible Situations When
Creating Circuit Diagrams

Possible Situations When
Creating Circuit Diagrams

Explanation

Remedy

Cannot enter contact or relay
in circuit diagram

Pico is in Run mode

Select Stop mode.

Time switch switches at
wrong times

Incorrect time or time switch
parameters

Check time and
parameters.

Cannot select analog
comparator ‘Ax’

Pico ac versions have no analog
inputs

Use Pico dc for
comparing analog
values.

Cannot select time switch
contacts

Pico has no clock

‘-NC’ version does
not have a clock.

When using a memory
module Pico will display the
message ‘PROG INVALID’

Pico memory module contains no
circuit diagram

Change the version
of Pico or change the
circuit diagram in
the memory module.

Circuit diagram on the memory
module uses contacts /relays that
Pico does not recognize:

• Do not use “-NC” versions

for time switch functions

• Analog inputs only with DC

controllers

Current flow display does not
show modifications to the
circuit connections

Pico is in Stop mode

Select Run mode.

Operation / connection not
performed

Check the circuit
diagram and
parameter sets and
modify as required.

Relay does not activate coil

Incorrect parameter values / time

• Analog value comparison

is incorrect

• Time value of timing relay

is incorrect

• Function of timing relay is

incorrect

Relay ‘Q’ or ‘M’ does not pick
up

Relay coil has been wired up
several times

Check coil field
entries.

Input not detected

Loose terminal contact

Check installation
instructions, and
external wiring.

No voltage to switch/button

Broken wire

Pico input is faulty

Replace the Pico.