Inside Pico 8-3

Determine Cycle Time of
Circuit Diagrams

The maximum cycle time of a circuit diagram must be known in order
to determine the maximum counter frequency or reaction time of
Pico.

Blank Cycle Time Calculation Tables can be found on page A-13 of
this manual.

1760-L12xxx Cycle Time

For 1760-L12xxx, the cycle time can be calculated as follows:

List of Times for Processing Function Relays

Function

Number

Time Duration
in µs

Total

Basic pulse

1

210

Refresh

1

3500

Contacts and bridged contact fields

20

Coils

20

Total rungs from the first one to the last
one, with empty ones in between

50

Connecting lines (only

)

20

Timing relays

Counters

Analog value function relays

Total

Number

1

2

3

4

5

6

7

8

Timing relays in µs

20

40

80

120

160

200

240

280

Counters in µs

20

50

90

130

170

210

260

310

Analog value processors in µs 80

100

120

140

160

180

220

260

,

,